SELECTION GUIDE

Vertiv Ups selection starts with measurable constraints

This guide turns an early requirement into a comparison-ready record. It does not replace a site study, protective-device review or local code assessment by qualified professionals.

Input table for a first-pass shortlist

Decision inputRecordWhy it matters
Continuous loadkW and kVA, measured or scheduledDefines capacity and exposes power-factor assumptions.
Input / outputRated voltage, phase, 50/60 HzAligns source, bypass and downstream distribution.
AutonomyMinutes at stated kWConnects battery sizing to the actual supported load.
RedundancyN, N+1, 2N or otherStates the capacity remaining after a planned or unplanned loss.
Power qualityTHD, power factor, source toleranceFrames rectifier, generator and nonlinear-load interaction.
EnvironmentTemperature, altitude, access, coolingIdentifies derating and maintainability constraints.
InterfacesModbus TCP, dry contacts, network cardDefines alarms, status visibility and integration ownership.

Use manufacturer data at the specified operating point. A “96% efficiency” statement is incomplete without load percentage, operating mode, voltage and test basis. Likewise, runtime must be tied to battery type, temperature, age assumption and discharge rate.

Configuration checkpoints

Work through the power path in order. Each confirmed item reduces the chance that a later installation constraint overturns the original shortlist.

  • Source: normal and bypass supplies, voltage window, frequency and generator interaction.
  • Load: steady demand, startup behavior, nonlinear content and growth allowance.
  • Distribution: maintenance bypass, interrupting capacity, SCCR and selective coordination responsibilities.
  • Battery: autonomy target, cabinet location, ventilation, replacement access and monitoring.
  • Operations: alarm routing, trained responders, spares and planned service windows.

Evidence to request before approval

Published data

Series data sheet, dimensional drawing, heat rejection, efficiency curve, overload behavior and applicable compliance declaration.

Project documents

Approved single-line, protection study inputs, layout, cable schedule, commissioning plan and accepted alarm matrix.

Repeatable checks

Record incoming conditions, applied load, operating mode, measurement points, transfer sequence and observed alarms during acceptance.

High utilization or conservative margin?

Running near the preferred load band may improve capital efficiency and keep modules well utilized. More margin can support growth and high-temperature operation, but it adds footprint, battery implications and initial cost. Compare both cases using the same load schedule and explicitly state which margin covers growth and which covers redundancy.

Battery runtime is not a fixed label

Cold or aged batteries, higher-than-planned load and repeated discharge events reduce autonomy. Treat runtime calculations as a defined condition, then confirm commissioning and maintenance methods. Energized testing and protective settings must be handled by qualified personnel.